Specifications
- Construction = 18/19 swg
- Triple Stage filtration
- EU6 – Prefilter (95% down to 5 micron)
- Hygieno brand pre filter
- EU14 – HEPA Filter – Supply (99.999% down to 0.3 micron)
- AAF brand pre filter
- EU7 – INTERMEDIATE FILTER – Supply / Exhaust (95% down to 3 micron)
- Hygieno brand pre filter
- Balanced Motor
- Internal covings for easy cleaning 2 side
- SS 304 Double walled Side Panels
- DOP Test port at upstream of HEPA filter
- Differential Pressure Gauge : 2 Nos to monitor pressure drop across two stages of filters.
- On / Off Switch for Motor
- 5/15 Amp Switch Socket for external equipment
- Fluorescent Light with Milky White Diffuser
Accessories Made Available
- Alarm for blower tripping with Fault Acknowledgement & Reset Switch
- Flame Proof Execution
- Front Anti Static PVC Curtains (for warehouse applications)
Documents
- MOC test certificates & OQ , PQ , IQ , DQ
Operating Conditions
- Air cleanliness
- ISO Class 5 (ISO 14644-1:1999 (E))
- Air Velocities
- 0.45 ± 0.05 mps
- Air Flow
- Vertical – Recirculatory
- Noise Level
- Less than 67 dB
- Vibration Level
- Minimum
- Power Supply
- 230V AC 1-Ø 50HZ